Certify Twisted Pair Cabling
Settings for Twisted Pair Tests
47
Test Limit
Select the correct test limit for the job. To see a different
group of limits, tap MORE, then tap the name of a
group.
Store Plot Data
Off : The tester does not save plot data for frequency-
domain tests or for the HDTDR/HDTDX analyzers. You
can see the plots before you save the test and exit the
results screen. The saved results show frequency-domain
measurements in a table and do not include the HDTDR/
HDTDX plots.
On : The tester saves plot data for all frequency-
domain tests required by the selected test limit and for
the HDTDR/HDTDX analyzers.
HDTDR/HDTDX
Fail/Pass* only: The tester shows HDTDR and HDTDX
analyzer results only for Autotests with
PASS*, FAIL*, or
FAIL results.
All Autotests: The tester shows HDTDR and HDTDX
analyzer results for all Autotests.
Never: The tester never shows HDTDR or HDTDX
analyzer results. This setting also disables the automatic
diagnostics, so the FAULT INFO screens never show.
To get HDTDR/HDTDX analyzer results you can also tap
TOOLS > Diagnostics.
For more information about the HDTDR and HDTDX
analyzers, see the Technical Reference Handbook.
Bi-directional
This setting shows only when you select a patch cord test
limit. It is used mainly by patch cord manufacturers to
make the Autotest time shorter.
On: The tester does tests in both directions.
Off: The tester does tests in only one direction, which
decreases the Autotest time.
Table 3. Settings for Twisted Pair Tests(cont.)