QUANTUM™ COMPRESSOR CONTROL PANEL
Page 20 OPERATION
greater than this setpoint. This setpoint helps avoid
forced unloading.
Low Process Temperature Force Unload - If the
Process Temperature is less than or equal to this
setpoint, the compressor will be forced to unload
until the Process Temperature is greater than this
setpoint. This setpoint helps avoid the low Process
Temperature alarm or shutdown.
Low Process Temperature Alarm - If the Process
Temperature is less than or equal to this setpoint, for
the alarm time delay, an alarm occurs.
Low Process Temperature Shutdown - If the
Process Temperature is less than or equal to this
setpoint, for the shutdown time delay, the
compressor will shut down.
Low Process Temperature Alarm Delay - The
minimum time in seconds that the Process
Temperature is less than or equal to the low Process
Temperature alarm setpoint before notification of the
alarm.
Low Process Temperature Shutdown Delay - The
minimum time in seconds that the Process
Temperature is less than or equal to the low Process
Temperature shutdown setpoint before the
compressor will shut down.
Process Temperature Control