Alarms/Shutdowns Messages
When a Shutdown occurs, the display backlight will flash
on and off to alert an operator of the shutdown. This visual
alarm will help get the attention of the operator in a noisy
engine room environment where audible alarms may not
be heard. Pressing any key on the keypad will clear the
flashing backlight.
Following is the alphabetical listing of all the possible
alarms:
Analog Board 1 Comm. Fail - Shutdown - It has been
detected that the program is no longer able to
communicate to Analog Board 1.
Analog Board 2 Comm. Fail - Shutdown - It has been
detected that the program is no longer able to
communicate to Analog Board 2.
Auxiliary #1 Alarm - The Auxiliary #1 input module has
been setup to indicate an alarm when it is de-energized
and it became de-energized.
Auxiliary #1 Shutdown - The Auxiliary #1 input module
has been setup to indicate a shutdown when it is de-
energized and it became de-energized.
Auxiliary #2 Alarm - The Auxiliary #2 input module has
been setup to indicate an alarm when it is de-energized
and it became de-energized.
Auxiliary #2 Shutdown - The Auxiliary #2 input module
has been setup to indicate a shutdown when it is de-
energized and it became de-energized.
Auxiliary #3 Alarm - The Auxiliary #3 input module has
been setup to indicate an alarm when it is de-energized
and it became de-energized.
Auxiliary #3 Shutdown - The Auxiliary #3 input module
has been setup to indicate a shutdown when it is de-
energized and it became de-energized.
Auxiliary #4 Alarm - The Auxiliary #4 input module has
been setup to indicate an alarm when it is de-energized
and it became de-energized.
Auxiliary #4 Shutdown - The Auxiliary #4 input module
has been setup to indicate a shutdown when it is de-
energized and it became de-energized.
Auxiliary #5 Alarm - The Auxiliary #5 input module has
been setup to indicate an alarm when it is de-energized
and it became de-energized.
Auxiliary #5 Shutdown - The Auxiliary #5 input module
has been setup to indicate a shutdown when it is de-
energized and it became de-energized.
Auxiliary #6 Alarm - The Auxiliary #6 input module has
been setup to indicate an alarm when it is de-energized
and it became de-energized.
Auxiliary #6 Shutdown - The Auxiliary #6 input module
has been setup to indicate a shutdown when it is de-
energized and it became de-energized.
Auxiliary #7 Alarm - The Auxiliary #7 input module has
been setup to indicate an alarm when it is de-energized
and it became de-energized.
Auxiliary #7 Shutdown - The Auxiliary #7 input module
has been setup to indicate a shutdown when it is de-
energized and it became de-energized.
Auxiliary #8 Alarm - The Auxiliary #8 input module has
been setup to indicate an alarm when it is de-energized
and it became de-energized.
Auxiliary #8 Shutdown - The Auxiliary #8 input module
has been setup to indicate a shutdown when it is de-
energized and it became de-energized.
Balance Piston Failure Shutdown - Balance piston
control was enabled in Factory Setup. There are three (3)
conditions that will cause a Balance Piston Failure
Shutdown:
1. If the difference between Discharge Pressure and
Suction Pressure is less than 60 lb. and the
Balance Piston output module (digital output
module 12) is de-energized, then the Balance
Piston pressure must be 1.1 times Suction
Pressure plus or minus 15 lb.
2. If the difference Discharge Pressure and Suction
Pressure is greater than or equal to 60 lb. and
the Balance Piston output module (digital output
module 12) is de-energized, then the Balance
Piston pressure must be 50 lb. below Discharge
Pressure plus or minus 15 lb.
3. If the Balance Piston output module (digital
output module 12) is energized, then Balance
Piston pressure must be within 20lb. of Oil
Pressure.
Compressor Aux. Failure - This shutdown message is
issued if while the compressor is running, the Compressor
Auxiliary input module, which receives feedback from the
motor starter, becomes de-energized.
Compressor Interlock Failure - This shutdown message
is issued if while the compressor is running the
Compressor Auxiliary input module becomes de-energized
for 5 seconds.
Compressor Starting Failure - Aux. - This shutdown
message is displayed if after 30 seconds from sending the
compressor start command, the compressor auxiliary input
module is still not energized.
Compressor Starting Failure - Low Motor Amps - This
shutdown message is displayed if after 30 seconds from
sending the compressor start signal, the Motor Amps
reading is not greater than the Low Motor Amps Shutdown
setpoint.
Compressor Stopping Failure - Aux. - This shutdown
message is issued if while stopping the compressor, after
8 seconds from the compressor stop command the
compressor auxiliary is energized. While this condition is
present, the Oil Pump (if available) is on and Liquid
Injection (if available) is allowed on and the Slide Valve is
unloaded to 0% to safeguard the compressor.
Compressor Stopping Failure - Motor Amps - This
shutdown message is issued if while stopping the
compressor, after 12 seconds from the compressor stop
command the Motor Current reading is above the Low
Motor Amps Shutdown setpoint. While this condition is
present, the Oil Pump (if available) is on, and Liquid