Conformity with UL standards and CSA standards (cUL-listed for Canada) (continued)
Required
torque lb-in
(Nm)
Wire size AWG (mm
2
)
Main terminal
L1/R, L2/S, L3/T U, V, W
Power supply voltage
Nominal applied motor
Inverter type
HD/MD/LD mode
Class J fuse size (A)
Circuit breaker trip size (A)
Main terminal
Aux. control power supply
Aux. Fan power supply
60°C Cu wire
75°C Cu wire
Remarks
60°C Cu wire
75°C Cu wire
Remarks
Aux. control power supply
Aux. fan power supply
0.4 FRN0.4G1
-4 3
0.75 FRN0.75G1
-4 6
5
10.6
(1.2)
- -
1.5 FRN1.5G1
-4 10 10
2.2 FRN2.2G1
-4 15 15
3.7
(4.0)*
FRN3.7G1
-4A
FRN4.0G1
-4E
HD
20 20
15.9
(1.8)
14
(2.1)
14
(2.1)
-
14
(2.1)
14
(2.1)
-
5.5 HD 30 30
12
(3.3)
FRN5.5G1
-4
LD
7.5
HD
40 40
10
(5.3)
12
(3.3)
FRN7.5G1
-4
LD
11
HD
60 50
10
(5.3)
FRN11G1
-4
LD
30.9
(3.5)
-
8
(8.4)
*1
*2
*3
-
8
(8.4)
*1
*2
*3
15
HD
70 60
FRN15G1
-4
LD
18.5
HD
90 75
6
(13.3)
FRN18.5G1
-4
LD
22
HD
100 100
4
(21.2)
6
(13.3)
6
(13.3)
FRN22G1
-4
LD
51.3
(5.8)
4
(21.2)
6
(13.3)
30
HD
125
3
(26.7)
4
(21.2)
FRN30G1
-4
LD
37
HD
175
125
2
(33.6)
3
(26.7)
-
FRN37G1
-4
LD
45
HD
200 150
2
(33.6)
2
(33.6)
-
FRN45G1-4
LD
55
HD
200
2
(33.6)
FRN55G1-4
LD
119.4
(13.5)
-
1/0
(53.5)
1/0
(53.5)
-
75
HD
250
175
FRN75G1
-4
LD
90
HD
300 200
2/0
(67.4)
4/0
(107.2)
FRN90G1
-4
MD/LD
110
HD
350 250
1/0×2
(53.5×2)
FRN110G1
-4
MD/LD
238.9
(27)
132
HD
400 300
1/0×2
(53.5×2)
2/0×2
(67.4×2)
FRN132G1
-4
MD/LD
160
HD
500 350
3/0×2
(85×2)
3/0×2
(85×2)
FRN160G1
-4
MD/LD
200
HD
600
4/0×2
(107.2×2)
250×2
(127×2)
FRN200G1
-4
MD/LD
Three-phase 400 V
220
FRN220G1
-4 HD
700
500
424.7
(48)
10.6
(1.2)
10.6
(1.2)
-
250×2
(127×2)
-
*2
*3
-
300×2
(152×2)
-
*2
*3
14
(2.1)
*1
*2
14
(2.1)
*1
*2
* 4.0 kW for the EU. The inverter type is FRN4.0G1-4E.
Note 1: Control circuit terminals Tightening torque: 6.1 lb-in (0.7 Nm), Recommended wire size: AWG 19 or 18 (0.65 to 0.82 mm
2
)
Note 2: A box (
) in the above table replaces S or E depending on the enclosure.
A box () in the above table replaces A or E depending on the shipping destination.
*1 No terminal end treatment is required for connection.
*2 Use 75°C Cu wire only.
*3 The wire size of UL Open Type and Enclosed Type are common. Please contact us if UL Open Type exclusive wire is necessary.