xii
Conformity with UL standards and CSA standards (cUL-listed for Canada) (continued)
Required torque
lb-in (Nm)
Wire size AWG (mm
2
)
Main terminal
L1/R, L2/S, L3/T U, V, W
Power supply voltage
Nominal applied motor
Inverter type
HD/MD/LD mode
Class J fuse size (A)
Circuit breaker trip size (A)
Main terminal
Aux. control power supply
Aux. Fan power supply
60°C Cu wire
75°C Cu wire
Remarks
60°C Cu wire
75°C Cu wire
Remarks
Aux. control power supply
Aux. fan power supply
250
MD 800
300×2
(152×2)
350×2
(177×2)
FRN220G1
-4
LD
400×2
(203×2)
*2
*3
400×2
(203×2)
*2
*3
280
FRN280G1
-4 HD
600
250×2
(127×2)
300×2
(152×2)
FRN280G1
-4 MD
315
FRN315G1
-4 HD
1000
300×2
(152×2)
350×2
(177×2)
FRN280G1
-4 LD
FRN315G1
-4 MD
355
FRN355G1
-4 HD
800
400×2
(203×2)
400×2
(203×2)
FRN315G1
-4 LD
FRN355G1
-4 MD
400
FRN400G1
-4 HD
1200
500×2
(253×2)
500×2
(253×2)
FRN355G1
-4 LD
450
MD
1400
600×2
(304×2)
600×2
(304×2)
FRN400G1
-4
LD
500
HD
1600
1200
350×3
(177×3)
400×3
(203×3)
FRN500G1
-4
LD
630
HD
2000 1400
500×3
(253×3)
600×3
(304×3)
Three-phase 400 V
710
FRN630G1
-4
LD 2200 1600
424.7
(48)
10.6
(1.2)
10.6
(1.2)
-
600×3
(304×3)
-
*2
*4
-
500×4
(253×4)
-
*2
*4
14
(2.1)
*1
*2
14
(2.1)
*1
*2
Note 1: Control circuit terminals Tightening torque: 6.1 lb-in (0.7 Nm), Recommended wire size: AWG 19 or 18 (0.65 to 0.82 mm
2
)
Note 2: A box (
) in the above table replaces S or E depending on the enclosure.
A box () in the above table replaces A or E depending on the shipping destination.
*1 No terminal end treatment is required for connection.
*2 Use 75°C Cu wire only.
*3 The wire size of UL Open Type and Enclosed Type are common. Please contact us if UL Open Type exclusive wire is necessary.
*4 It is showing the wire size for UL Open Type.
See additional material INR-SI47-1365 for UL Enclosed Type (Pack with TYPE1 kit).