vii
Conformity to the Low Voltage Directive in the EU (Continued)
Recommended wire size (mm
2
)
Main circuit
MCCB or
RCD/ELCB *1
Rated current
Main power
input *2
[L1/R, L2/S, L3/T]
Inverter’s
grounding [
G]
Power supply voltage
Nominal applied motor
Inverter type
HD/MD/LD mode
W/
DCR
W/o
DCR
W/
DCR
W/o
DCR
Inverter outputs
[U, V, W] *2
DC reactor
[P1, P(+)] *2
Braking resistor
[P(+), DB] *2
Control circuit
Aux. control power
supply [R0, T0]
Aux. fan power
supply [R1, T1]
0.4
FRN0.4G1
-4
0.75
FRN0.75G1
-4
5 -
1.5
FRN1.5G1
-4
5
10
2.2
FRN2.2G1
-4 15
1
3.7
(4.0)*
FRN3.7G1
-4A
FRN4.0G1
-4E
HD
10
20 1.5
1 1
5.5
HD 15 30
1
2.5 1.5 1.5
FRN5.5G1
-4
LD
7.5
HD
20 40 1.5 4 2.5 2.5
FRN7.5G1
-4
LD
11
HD
30 50 4 6 4 4
FRN11G1
-4
LD
15
HD
60 10 6 6
FRN15G1
-4
LD
18.5
HD
40
75
6
10
FRN18.5G1
-4
LD
22
HD
50 100 10
16 10
16
FRN22G1
-4
LD
30
HD
75 16 25 16
FRN30G1
-4
LD
1
37
HD
125
35 25
25
FRN37G1
-4
LD
45
HD
100
150
25
50 35 35
FRN45G1
-4
LD
1.5
55
HD
125 200 35 70 50 70
FRN55G1
-4
LD
2.5
-
75
HD
175 70 70 95
FRN75G1
-4
LD
4
90
HD
200 95 95 120
FRN90G1
-4
MD/LD
110
HD
250 50×2 150
FRN110G1
-4
MD/LD
132
HD
300 70×2
70×2
70×2
FRN132G1
-4
MD/LD
160
HD
350 185 240 300
FRN160G1-4
MD/LD
200
HD
300 120×2
FRN200G1
-4
MD/LD
Three--phase 400 V
220
FRN220G1
-4 HD
500
-
300
-
150×2 150×2
-
0.65
to
0.82
2.5
2.5
* 4.0 kW for the EU. The inverter type is FRN4.0G1-4E.
Note: A box (
) in the above table replaces S or E depending on the enclosure.
A box () in the above table replaces A or E depending on the shipping destination.
*1 The frame size and model of the MCCB or RCD/ELCB (with overcurrent protection) will vary, depending on the power transformer capacity.
Refer to the related technical documentation for details.
*2 The recommended wire size for main circuits is for the 70°C 600 V PVC wires used at a surrounding temperature of 40°C.