6-92
(MSB) (LSB)
15 14 8 7 10
%IW***0 Polling function code (1) Polling function code (2)
%IW***1 Polling function code (3) Polling function code (4)
%IW***2 Polling function code (1) data
%IW***3 Polling function code (2) data
%IW***4 Polling function code (3) data
%IW***5 Polling function code (4) data
%IW***6 Motor speed (M06)
%IW***7 Operation state (refer to * 6.5.8.1 (1))
%QW***8 Selecting function code (1) Selecting function code (2)
%QW***9 Selecting function code (3) Selecting function code (4)
%QW***10 Selecting function code (1) data
%QW***11 Selecting function code (2) data
%QW***12 Selecting function code (3) data
%QW***13 Selecting function code (4) data
%QW***14 Polling function code (1) Polling function code (2)
%QW***15 Polling function code (3) Polling function code (4)
Note: *** represents the SX bus station address set by "RSW1" and "RSW2".
Figure 6.5.18
(2) UPAC compatible format
When the UPAC compatible format is selected (U11=1)
, as shown in the figure below, out of the I/Q
area of the MICREX-SX, 51 words are used for each FRENIC-VG, with the lower 29 words are
used for read and upper 22 words are used for write.
(MICREX-SX FRENIC-VG) data
(22 words)
(MICREX-SX FRENIC-VG) data
(29 words)
(MSB) (LSB)
15 14 ・・・ ・・・ 1 0
51 words
MICREX-SX
I/Q area
Figure 6.5.19
FRENIC-VG
MICREX-SX
MICREX-SX
FRENIC-VG

Table of Contents

Related product manuals