6-96
(4) Standard format 2 (specified with 485No)
When the standard format 2 is selected (U11=3)
, as shown in the figure below, out of the I/Q area of
MICREX-SX, 16 words are used for each FRENIC-VG, with the lower 8 words are used for read
and upper 8 words are used for write.
(MICREX-SX FRENIC-VG) data
(8 words)
(MICREX-SX FRENIC-VG) data
(8 words)
(MSB) (LSB)
15 14 ・・・ ・・・ 1 0
16 words
MICREX-SX
I/Q area
Figure 6.5.24
(MSB) (LSB)
15 14 8 710
%IW***0 Polling function code 485No (1)
%IW***1 Polling function code 485No (2)
%IW***2 Polling function code (1) data
%IW***3 Polling function code (2) data
%IW***4 Function code monitor (1)
%IW***5 Function code monitor (2)
%IW***6 Motor speed (M06)
%IW***7 Operation state (refer to * 6.5.8.1 (1))
%QW***8 Selecting function code 485No (1)
%QW***9 Selecting function code 485No (2)
%QW***10 Selecting function code (1) data
%QW***11 Selecting function code (2) data
%QW***12 Speed command (S01)
%QW***13 Operation command/Di/RESET input (S06)
%QW***14 Polling function code 485No (1)
%QW***15 Polling function code 485No (2)
Note: *** represents the SX bus station address set by "RSW1" and "RSW2".
Figure 6.5.25
FRENIC-VG
MICREX-SX
MICREX-SX
FRENIC-VG