6.5 SX Bus Interface Card
6-95
Chap. 6
CONTROL OPTIONS
(3) Monitoring format
When the monitoring format is selected (U11=2)
, as shown in the figure below, out of the I/Q area
of the MICREX-SX, 16 words are used for each FRENIC-VG, with the lower 4 words are used for
read and upper 12 words are used for write.
(MICREX-SX FRENIC-VG) data
(12 words)
(MICREX-SX FRENIC-VG) data
(4 words)
(MSB) (LSB)
15 14 ・・・ ・・・ 1 0
16 words
MICREX-SX
I/Q area
Figure 6.5.22
(MSB) (LSB)
15 14 8 710
%IW***0 Polling function code (1) Polling function code (2)
%IW***1 Polling function code (3) Polling function code (4)
%IW***2 Polling function code (5) Polling function code (6)
%IW***3 Polling function code (7) Polling function code (8)
%IW***4 Polling function code (1) data
%IW***5 Polling function code (2) data
%IW***6 Polling function code (3) data
%IW***7 Polling function code (4) data
%IW***8 Polling function code (5) data
%IW***9 Polling function code (6) data
%IW***10 Polling function code (7) data
%IW***11 Polling function code (8) data
%QW***12 Polling function code (1) Polling function code (2)
%QW***13 Polling function code (3) Polling function code (4)
%QW***14 Polling function code (5) Polling function code (6)
%QW***15 Polling function code (7) Polling function code (8)
Note: *** represents the SX bus station address set by "RSW1" and "RSW2".
Figure 6.5.23
FRENIC-VG
MICREX-SX
MICREX-SX
FRENIC-VG