6.5 SX Bus Interface Card
6-103
Chap. 6
CONTROL OPTIONS
(2) When UPAC compatible format is selected
1 Control data (CW)
(MSB) (LSB)
15 8 7 0
0) FWD (Run forward command)
1) REV (Run reverse command)
2) X1
3) X2
4) X3
5) X4
6) X5
7) X6
8) X7
9) X8
10) X9
11) X11
12) X12
13) X13
14) X14
15) RST (RESET command)
FWD, REV and X1 to X14 are available when the link command is permitted as instructed in
"6.4.9.1 Link Command Permission Selection". RST is always available.
Note that the operation command (FWD/REV) specifications are different from when the UPAC
option is used as shown below (available soon for the UPAC option).
The AND condition of the operation commands defined in the UPAC option specifications is
invalidated (deleted) for the SX bus option (when the UPAC compatible format is selected)
(available soon for the UPAC option).
Figure 6.5.26
0: OFF,
1: ON
When UPAC option is applied
Terminal table
Touch panel
Link (S06)
Control data: FWD/REV
(Command from UPAC)
ON
Dynamic SW
OFF
AND
Operation
command
Operation
command
When SX option (UPAC compatible format) is applied
Terminal table
Touch panel
Link (S06)
Control data: FWD/REV
(Command from SX)
ON
Dynamic SW
OFF
Operation
command
Operation
command