6.5 SX Bus Interface Card
6-105
Chap. 6
CONTROL OPTIONS
5 VG DO1 (standardDIOA: 13 bits)
(MSB) (LSB)
15 8 7 0
0) Y1
1) Y2
2) Y3
3) Y4
4) Y5A
5) Unused
6) Unused
7) Unused
8) Y11
9) Y12
10) Y13
11) Y14
12) Y15
13) Y16
14) Y17
15) Y18
6 Acceleration time, deceleration time
(MSB) (LSB)
15 14 1312 11 1098765432 1 0
Acceleration (deceleration) time data
Acceleration (deceleration) time data: 0.1s/1d
7 Selecting function code address and selecting function code data
(MSB) (LSB)
15 14 1 0
Selecting function code 1 address
Selecting function code 1 data
Selecting function code 2 address
Selecting function code 2 data
"Selecting function code 1, 2 address" (16 bits each) write the link number corresponding to the
function code selected by MICREX-SX. Write the data to "Selecting function code 1, 2 data".
Note: Upon selecting, be sure to write the link number and data together.
Writing from this frame to the S code is prohibited. For a command equivalent to the S code,
give commands from each dedicated frame.
0: OFF, 1: ON