6-156
Table 6.7.3 LED status indicator specifications
Status
L.RUN L.ERR SD RD
Operation Status
Normal communications
Normally communicating. But sometimes a CRC error occurs
due to electrical noise.
Received data contains a CRC error, so the communications
card cannot respond.
Data destined for this station does not come.
Responding to polling. But refresh data received contains a
CRC error.
Data destined for this station contains a CRC error.
No data destined for this station. Or data destined for this
station cannot be received due to electrical noise.
●○ Baud rate, station address incorrectly specified.
(0.8-second
intervals)
Baud rate or station address changed before completion.
Link has not been started up.
Data cannot be received due to wire break, power down,
hardware reset in progress,
er3
power area failure
: ON, : OFF, : Blinking (It may seem to be ON depending on the current transmission baud rate.)
Note 1: If LED lights due to a pattern other than the above, it can be assumed hardware error has occurred.
Contact us.