Revision 8 SLG 700 SmartLine Level Transmitter User’s Manual Page 115
Critical Diag
Low Power Mode (R)
Yes
No
Yes: Sensor is in low power mode
Reflectn Ref Loc (R)
OK
FAULT
FAULT: Reflection reference cannot be located
Ref Plane Offset (R)
OK
FAULT
FAULT: Reference plane offset is invalid
Unlic Intf Meas (R)
OK
FAULT
FAULT: Unlicensed Interface measurement
option
Unlic Sat Steam (R)
OK
FAULT
FAULT: Unlicensed Saturated Steam
application option
Unlic Low DC App (R)
OK
FAULT
FAULT: Unlicensed Low DC application option
ModelNumMismatch (R)
Yes
No
Yes: Mismatch between Sensor and Comm
Module Model Numbers
Sensr DB Corrupt (R)
Yes
No
Yes: The Sensor Module database is corrupt
and requires reset
Reset Sensr DB
(Sensor DB corrupt only)
Perform reset of Sensor Module database to
SLG720 factory defaults
Comm DB Corrupt (R)
Yes
No
Yes: The Comm Module database is corrupt and
requires reset
Reset Comm DB
(Comm DB corrupt only)
Perform reset of Comm Module database to
SLG720 factory defaults