Page 166 SLG 700 SmartLine Level Transmitter User’s Manual Revision 8
9.3 Hazardous Locations Certifications
AGENCY
TYPE OF PROTECTION
COMM
FIELD
PARAMETERS
CSA
cCSAus
(Canada and
USA)
Certificate #
70016542
Explosion Proof with
intrinsically safe probe:
Class I, Division 1, Groups A, B, C,
D;
Class I, Zone 0/1 AEx d[ia] IIC
T6..T5 Ga/Gb
Ex d[ia] IIC T6..T5 Ga/Gb
Dust Ignition Proof:
Class II, III, Division 1, Groups E,
F, G; T5 or T6
Class II Zone 21 AEx tb IIIC T95
o
C
DIP A21/II, III /1/EFG/Ex tb IIIC
T95
o
C
All
Note 1
Intrinsically Safe:
Class I, II, III, Division 1, Groups A,
B, C, D, E, F, G; T4
Class 1 Zone 0 AEx ia IIC T4 Ga
Ex ia IIC T4 Ga
Class I Zone 2 AEx ic IIC T4 Gc
Ex ic IIC T4 Gc
4-20 mA / HART
Note 2a
FOUNDATION
Fieldbus / FISCO
Note 2b/2c
Non-incendive with intrinsically
safe probe:
Class I, Division 2, Groups A, B, C,
D; T6..T5
Class I, Zone 0/2 AEx nA[ia] IIC
T6..T5 Ga/Gc
Ex nA[ia] IIC T6..T5 Ga/Gc
4-20 mA / HART
Note 1
FOUNDATION
Fieldbus / FISCO
Note 1
Enclosure: Type 4X/ IP66/ IP67.
Dual Seal in accordance with
ANSI/ISA 12.27.01
All
All
Canadian Registration Number (CRN):
All SLG 700 models are registered in
all provinces and territories in
Canada.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell SmartLine SLG 700 and is the answer not in the manual?

Honeywell SmartLine SLG 700 Specifications

General IconGeneral
BrandHoneywell
ModelSmartLine SLG 700
CategoryTransmitter
LanguageEnglish

Related product manuals