Table 6-1 Refrigerant charge amount
Indoor Unit Outdoor Unit Refrigerant Charge Amount (L) (L is total
one-way pipe length) (kg)
- 0 m < L ≤ 10
m
10 m < L ≤
60 m
60 m < L ≤
100 m
NetCol8000-
A045D
NetCol500-A060/
NetCol500-A120
system 1/
NetCol500-A120
system 2
9.4 9.4 + (L – 10)
x 0.21
9.4 + (L – 10)
x 0.28
NetCol500-A080 13.4 13.4 + (L –
10) x 0.21
13.4 + (L –
10) x 0.28
NetCol8000-
A045D
(including a
low
temperature
component)
NetCol500-A060/
NetCol500-A120
system 1/
NetCol500-A120
system 2
32.9 32.9 + (L –
10) x 0.21
32.9 + (L –
10) x 0.28
NetCol8000-
A045U
NetCol500-A060/
NetCol500-A120
system 1/
NetCol500-A120
system 2
8.8 8.8 + (L – 10)
x 0.21
8.8 + (L – 10)
x 0.28
NetCol500-A080 12.8 12.8 + (L –
10) x 0.21
12.8 + (L –
10) x 0.28
NetCol500-W055 9.6 9.6 + (L – 10)
x 0.19
-
NetCol8000-
A045U
(including a
low
temperature
component)
NetCol500-A060/
NetCol500-A120
system 1/
NetCol500-A120
system 2
32.3 32.3 + (L –
10) x 0.21
32.3 + (L –
10) x 0.28
NetCol8000-
A090D
system 1
NetCol500-A060/
NetCol500-A120
system 1
9.4 9.4 + (L – 10)
x 0.21
9.4 + (L – 10)
x 0.28
NetCol500-A080 13.4 13.4 + (L –
10) x 0.21
13.4 + (L –
10) x 0.28
NetCol8000-
A090D
system 2
NetCol500-A060/
NetCol500-A120
system 2
9.4 9.4 + (L – 10)
x 0.21
9.4 + (L – 10)
x 0.28
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 6 Power-On Commissioning
Issue 05 (2020-10-10) Copyright © Huawei Technologies Co., Ltd. 155