Indoor Unit Outdoor Unit Refrigerant Charge Amount (L) (L is total
one-way pipe length) (kg)
NetCol500-A080 13.4 13.4 + (L –
10) x 0.21
13.4 + (L –
10) x 0.28
NetCol8000-
A090D
system 1
(including a
low
temperature
component)
NetCol500-A060/
NetCol500-A120
system 1
32.9 32.9 + (L –
10) ×0.21
32.9 + (L -
10) × 0.28
NetCol8000-
A090D
system 2
(including a
low
temperature
component)
NetCol500-A060/
NetCol500-A120
system 2
32.9 32.9 + (L –
10) x 0.21
32.9 + (L –
10) x 0.28
NetCol8000-
A055D
NetCol500-A080 16.5 16.5 + (L –
10) x 0.23
16.5 + (L –
10) x 0.31
NetCol500-A110 23 23 + (L – 10)
x 0.23
23 + (L – 10)
x 0.31
NetCol8000-
A055D
(including a
low
temperature
component)
NetCol500-A080 43 43 + (L – 10)
x 0.23
43 + (L – 10)
x 0.31
NetCol8000-
A060D
NetCol500-A080 15.5 15.5 + (L –
10) x 0.23
15.5 + (L –
10) x 0.31
NetCol500-A110 22 22 + (L – 10)
x 0.23
22 + (L – 10)
x 0.31
NetCol8000-
A060D
(including a
low
temperature
component)
NetCol500-A080 42 42 + (L – 10)
x 0.23
42 + (L – 10)
x 0.31
NetCol8000-
A060U
NetCol500-A080 15.5 15.5 + (L –
10) x 0.23
15.5 + (L –
10) x 0.31
NetCol500-A110 22 22 + (L – 10)
x 0.23
22 + (L – 10)
x 0.31
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 6 Power-On Commissioning
Issue 05 (2020-10-10) Copyright © Huawei Technologies Co., Ltd. 156