NO TICE
User operator can access customer and delivery parameters. The parameters
on the Advanced menu are delivery parameters. User admin can access
customer, delivery, maintenance, and R&D parameters. The parameters on the
Advanced menu are R&D parameters.
To prevent the eect of misoperations on the system, log in as user operator
before modifying parameters. Conrm with Huawei technical support before
modifying parameters which cannot be
modied by user operator. Otherwise,
Huawei will not be liable for any consequences of the modication performed
by the user.
Only certied professionals are allowed to modify the advanced parameters.
Unauthorized modications may lead to device malfunction or damage.
For system security purposes, change the preset password after the rst login.
After login, your permission will become invalid automatically if no operation is
performed for 3 minutes (congurable). For security purposes, tap
at the lower-right corner of the screen to manually log out after you have
completed all operations.
Step 4 Set related parameters and tap Next until the home screen is displayed.
Tab
Parameter Description
Select
Language
Language Species the display language.
Date and
Time Settings
Date format Species the date format.
Date settings Species the date.
Time zone Species the time zone.
Time Species the time.
Teamwork
Settings
Teamwork group No. Species the planned teamwork group
number. This parameter should be the
same for all units in the same
teamwork group.
System address Species the planned unit address. The
addresses of units in the same
teamwork group must be unique.
Networking mode Species the networking mode for
teamwork control. The networking
mode selected on the screen must
match the actual networking mode.
Otherwise, the teamwork function is
unavailable.
Number of systems in
this group
Species the total number of units in
this group. The value is an integer
ranging from 1 to 32.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 6 Power-On Commissioning
Issue 05 (2020-10-10) Copyright © Huawei Technologies Co., Ltd. 170