Tab Parameter Description
Number of running
systems in this group
Species the number of running units
in this group. The value is an integer
ranging from 1 to the value of
Number of systems in this group.
Teamwork function Species whether to enable the
teamwork function. Set this parameter
based on onsite heat load distribution.
Disable: A unit operates
independently.
Enable: A unit operates in team
with other units.
System
Optional
Parts
Cold aisle sensor Enables or disables a sensor.
Hot aisle sensor Enables or disables a sensor.
Cold aisle
temperature and
humidity sharing
This function can be enabled only
when at least one smart cooling
product in the group is equipped with
cold aisle T/H sensors. If this function
is enabled, the master unit in the
teamwork group collects the cold aisle
temperature and humidity values from
all units equipped with cold aisle
sensors, and synchronizes the
temperature and humidity values to all
units after logical calculation.
After this function is enabled, the
master unit synchronizes the
temperature and humidity control type
and setpoints to all slave units.
Hot aisle temperature
and humidity sharing
This function can be enabled only
when at least one smart cooling
product in the group is equipped with
hot aisle T/H sensors. If this function is
enabled, the master unit in the
teamwork group collects the hot aisle
temperature and humidity values from
all units equipped with hot aisle
sensors, and synchronizes the
temperature and humidity values to all
units after logical calculation.
After this function is enabled, the
master unit synchronizes the
temperature and humidity control type
and setpoints to all slave units.
Low temperature
component
Species whether a low temperature
component is used.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 6 Power-On Commissioning
Issue 05 (2020-10-10) Copyright © Huawei Technologies Co., Ltd. 171