Tab Parameter Description
System
Settings
Dual power supply
setting
Set this parameter as required.
Primary power only: Select this
option when the dual-power model
is connected to the primary power
only.
Primary power
rst: Select this
option when the dual-power model
is connected to two power supplies.
Outdoor unit
condensate mode
Air-cooled: The outdoor unit is an
air-cooled outdoor unit.
Water-cooled: The outdoor unit is a
water-cooled module.
Temp control
intelligent monitoring
board
A temperature control intelligent
monitoring board is used to monitor
the outdoor environment.
Check the cover of the electric control
box of the outdoor unit.
If there is an intelligent
temperature control monitoring
board, set this parameter to Yes.
If there is no intelligent
temperature control monitoring
board, set this parameter to No.
Smart diagnosis
function
Enable: If there is an intelligent
temperature control monitoring
board, this function is enabled to
start refrigerant shortage detection.
Disable: The smart diagnosis
function is disabled.
Conditions for starting refrigerant
shortage detection:
No low temperature component is
congured.
Altitude: ≤ 2000 m
7.5 m ≤ equivalent pipe length of
the one-way pipe ≤ 100 m
–8 m ≤ vertical distance between
the indoor and outdoor units ≤ +30
m
5°C ≤ outdoor ambient temperature
≤ 40.5°C