Tab Parameter Description
In-cabinet water
overow alarm action
Set the action of the device if there is
water overow in the cabinet based on
the actual scenario.
Shutdown: The device shuts down
when an in-cabinet water overow
alarm is generated.
Inactivity: The device runs as usual
when an in-cabinet water overow
alarm is generated.
Only indoor fan running: Only the
indoor fan runs when an in-cabinet
water
overow alarm is generated.
Humidier stopped: Only the
humidier is stopped when an in-
cabinet water overow alarm is
generated.
T/H Sensor Temperature and
humidity control type
When the application scenario is non-
aisle containment, you are advised to
choose Return air. Choose Cold aisle
if cold aisle T/H sensors are installed.
Hot aisle is not recommended.
Temperature setpoint After the temperature and humidity
control type and the temperature
value under this type are set, the
device performs cooling or heating
based on the settings.
Return air temperature: 26–35°C
recommended
Supply air temperature: 18–24°C
recommended
Cold aisle temperature: 18–24°C
recommended
Hot aisle temperature: 26–35°C
recommended
Humidity setpoint After the temperature and humidity
control type and the humidity value
under this type are set, the device
performs management based on the
settings.
40%–60% is recommended.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 6 Power-On Commissioning
Issue 05 (2020-10-10) Copyright © Huawei Technologies Co., Ltd. 176