Tab Parameter Description
DO_1 If this parameter is set to Smoke &
Water only, DO_1 acts according to
DO_1 action when a smoke or
water overow alarm is generated.
If this parameter is set to Critical
alarm, DO_1 acts according to
DO_1 action when a critical alarm
is generated.
If this parameter is set to Major,
DO_1 acts according to DO_1
action when a major alarm is
generated.
If this parameter is set to Alarm,
DO_1 acts according to DO_1
action when a critical alarm, major
alarm, or warning is generated.
If this parameter is set to Startup
status, DO_1 acts according to
DO_1 action when the unit is
started.
If this parameter is set to None, no
alarm is generated when DO_1 is
disconnected.
DO_2
For details, see DO_1 description.
Floor water overow
alarm action
Set the action of the device if there is
water overow on the oor based on
the actual scenario.
Shutdown: The device shuts down
when a oor water overow alarm
is generated.
Inactivity: The device runs as usual
when a
oor water overow alarm
is generated.
Only indoor fan running: Only the
indoor fan runs when a
oor water
overow alarm is generated.
Humidier stopped: Only the
humidier is stopped when a oor
water overow alarm is generated.
NetCol8000-A(045, 055, 060, 090, 120) In-room Air
Cooled Smart Cooling Product
User Manual 6 Power-On Commissioning