75 - 105 TON MODELS
MODEL SIZE 075 080 090 105
Static Pressure Range (min. to max. ESP) 0–2” 0–2” 0–2” 0–2”
Optional Exhaust Fan
Quantity Fans/Motors 2 / 1 2 / 1 2 / 1 2 / 1
Type FC FC FC FC
Size 20-18 20-18 20-18 20-18
Motor Size Range (min. to max. HP) 5–30 5–30 5–30 5–30
Airow Range (min. to max. CFM) 4000–36000 4000–36000 4000–36000 4000–36000
Static pressure range (min. to max. IWG) 0–2” 0–2” 0–2” 0–2”
Optional Return Fan
Quantity Fans/Motors 2 / 2 2 / 2 2 / 2 2 / 2
Type Plenum Plenum Plenum Plenum
Size 270 270 270 270
Motor Size Range (min. to max. HP) 10–30 10–30 10–40 10–40
Airow Range (min. to max. CFM) 40000-32000 40000-32000 4000–36000 4000–36000
Static pressure range (min. to max. IWG) 0–3” 0–3” 0–3” 0–3”
Evaporator Coil R-410A
Size (square feet) 56.9 56.9 56.9 56.9
Number of rows/ns per inch 3/17 3/17 3/17 5/17
Tube Diameter 3/8" 3/8" 3/8" 3/8"
Condenser Coil (R410A)
Size (square feet) 164 164 164 164
Number of rows/ns per inch 1/21 1/21 1/21 1/21
Tube Diameter/Surface 1 mm microchannel 1 mm microchannel 1 mm microchannel 1 mm microchannel
Condenser Fans
Quantity 6 6 6 6
Type Prop. Prop. Prop. Prop.
Diameter (inches) 36 36 36 36
Power (hp each) 2 2 2 2
Power (hp each) 2 2 2 2
Filters - 2” Throwaway (Pre-Filter Position)
Quantity 10 / 15 10 / 15 12 / 18 12 / 18
Size (length x width) (in.) 25x16 / 25x20 25x16 / 25x20 25x16 / 25x20 25x16 / 25x20
Total Filter Face Area (square feet) 77.1 77.1 92.5 92.5
Filters - 2” Cleanable (Pre-Filter Position)
Quantity 10 / 15 10 / 15 12 / 18 12 / 18
Size (length x width) (in.) 25x16 / 25x20 25x16 / 25x20 25x16 / 25x20 25x16 / 25x20
Total Filter Face Area (square feet) 77.1 77.1 92.5 92.5
Filters - 2” Pleated, 30% Efficient (Pre-Filter Position)
Quantity 10 / 15 10 / 15 12 / 18 12 / 18
Size (length x width) (in.) 25x16 / 25x20 25x16 / 25x20 25x16 / 25x20 25x16 / 25x20
Total Filter Face Area (square feet) 77.1 77.1 92.5 92.5
TABLE 3 - PHYSICAL DATA (CONT'D)