Table 8: SRX1500 Services Gateway Environmental Specifications
ValueDescription
No performance degradation to 10,000 ft (3048 m)Altitude
Normal operation ensured in relative humidity range of 5% to
90%, noncondensing
Relative humidity
•
Normal operation ensured in temperature range of 32° F (0°
C) to 104° F (40° C)
•
Nonoperating storage temperature in shipping container:
–40° F (–40° C) to 158° F (70° C)
Temperature
300 BTU/hourMaximum thermal output
30 dBNoise level
Related
Documentation
SRX1500 Services Gateway Physical Specifications on page 17•
• Site Preparation Checklist for the SRX1500 Services Gateway on page 18
• General Site Installation Guidelines for the SRX1500 Services Gateway on page 20
Site Preparation Checklist for the SRX1500 Services Gateway
Table 9 on page 18 provides a checklist of tasks you need to perform when preparing a
site for installing the SRX1500 Services Gateway.
Table 9: Site Preparation Checklist for SRX1500 Services Gateway
Installation
NotesDate
Performed
ByAdditional InformationItem or Task
Power
“SRX1500 Services Gateway
Electrical Wiring Guidelines” on
page 31
Measure distance between
external power sources and
device installation site.
“Connecting the SRX1500
Services Gateway Grounding
Cable” on page 58
Locate sites for connectionof
system grounding.
“SRX1500 Services GatewayAC
Power Supply Electrical
Specifications” on page 33 and
“SRX1500 Services GatewayDC
Power Supply Electrical
Specifications” on page 34
Calculate the power
consumption and
requirements.
Environment
Copyright © 2017, Juniper Networks, Inc.18
SRX1500 Services Gateway Hardware Guide