NOTE: Each power supply must be connected to a dedicated AC power
feed and a dedicated external circuit breaker. We recommend that you
use a 15 A (250 VAC) minimum, or as permitted by local code.
4. Dress the power cord appropriately. Verify that the power cord does not block the air
exhaust and access to services gateway components or drape where people could
trip on it.
NOTE: The services gateway must be connected to earth ground during
normal operation. The protective earthing terminal on the side of the chassis
is provided to connect the services gateway to ground.
CAUTION: We recommend using a surge protector for the power connection.
Related
Documentation
Installing an AC Power Supply on the SRX1500 Services Gateway on page 53•
• Connecting an AC Power Cord to the SRX1500 Services Gateway on page 66
• Powering On the SRX1500 Services Gateway on page 68
• Powering Off the SRX1500 Services Gateway on page 69
Connecting an AC Power Cord to the SRX1500 Services Gateway
To connect the AC power cord:
1. Locate a replacement power cord with the type of plug appropriate for your
geographical location.
2. Connect the power cord to the power supply. Use a power cord retainer to hold the
power cord in place.
3. Insert the power cord plug into an external AC power source receptacle.
4. Verify that the power cord does not block the air exhaust and access to services
gateway components, or drape where people could trip on it. If the power supply is
correctly installed and functioning normally, the PWR LED glows steadily.
Related
Documentation
Connecting the SRX1500 Services Gateway to an AC Power Supply on page 65•
• Powering On the SRX1500 Services Gateway on page 68
Copyright © 2017, Juniper Networks, Inc.66
SRX1500 Services Gateway Hardware Guide