79
12.Averagingperio dofmin/maxPandQ
Theaveragingperiodusedinthecalculationofminimumandmaximumvaluesofpower(P)andflow(Q)canbe
adjusted.Theaveragingperiodisindicatedintheintervalof1…1440minutes.Readmoreabouttheaveragingperiod
ofmin./maxofPand
Qinparagraph7.5.

13.Heat/coolingshift(
hc
)
Thelimitforheat/coolingshift(
hc
)canbeadjustedintheSETUPloop,howeveronlyinmetersorderedasmetertype
6(heat/coolingmeter).Thevaluecanbeselectedintheinterval2…180.00Caswellasat250.00Ciftheuserwants
todisablethefunct ion.Thefunctionisenabledagainbysetting
thelimitatavalueinthevalidareaof2…180C.
Heat/coolingshiftispermanentlydisabledonothermetertypes,andthedisplaythusshows“Off”onallothermeter
typesthan6.Readmoreaboutheat/coolingshiftinparagraph7.4.
Metertype:1,2,3,4,5,
7 Metertype:6

Theframesaround“Off”illuminatesas
long as the primary key remains
activated.
Thefirstdigitflashesandeachdigitcan
nowbesetatavaluewithintherange
0…9.
Ifyouchooseavalueoutsidethevalid
interval(2…180.00C),thevalueis
automaticallyadjustedto250.00C,
whichindicatesthatthefunctionhas
beenswitchedoff.

Table of Contents

Other manuals for Kamstrup MULTICAL 603

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kamstrup MULTICAL 603 and is the answer not in the manual?

Kamstrup MULTICAL 603 Specifications

General IconGeneral
Flow SensorUltrasonic
Battery LifeUp to 16 years
Power SupplyBattery
Communication OptionsM-Bus, Wireless M-Bus, Modbus, BACnet
DisplayLCD
ApplicationHeating and Cooling
Pressure RatingPN16
ApprovalMID
AccuracyClass 2
Ambient Temperature Range55°C
Housing MaterialBrass

Related product manuals