Parameters
94 Operating manual for INVEOR α | DOC01539818 - 0004 | 2017-01 | V2.0 EN
5.082 Start-up error active Unit: integer
Relationship
to parameter:
4.233
Parameter
manual:
P. xy
Transfer status:
2
min.:
0 Own value
(to be entered!)
max.: 1
def.: 1
(V 03.70 and higher)
Start-up error is defined as follows: Actual value does not reach 10 % of the
rated motor frequency after 30 seconds (if nominal frequency < 10 %, the error
is not generated). If the acceleration time is parameterised as > 60 seconds,
half the acceleration time is used in place of the 30 seconds.
0 = Function disabled
1 = Function enabled
5.083 Deactivation error log 11 Unit: integer
Relationship
to parameter:
Parameter
manual:
P. xy
Transfer status:
2
min.: 0 Own value
(to be entered!)
max.: 10
def.: 0
(V 03.80 and higher)
If supplied with external 24 V, the logging of error no. 11 "Time out power" can
be suppressed here.
The error counter is not affected.
0 = Function disabled
1 = Function enabled