Step 3. Install a PCIe adapter.
Note: Carefully handle the PCIe adapter by its edges.
Figure 214. PCIe adapter installation
a. Align the PCIe adapter with the PCIe slot on the riser card. Carefully press the PCIe adapter
straight into the slot until it is securely seated and its bracket also is secured.
b. Rotate the PCIe adapter retention latch to the closed position.
Step 4. Install the riser assembly into chassis.
Figure 215. Riser assembly installation
a. Align the riser card with the riser slot on the system board. Carefully press the riser card
straight into the slot until it is securely seated.
b. Tighten the screw to secure the riser cage.
After you finish
1. Refer to Chapter 3 “Internal cable routing” on page 71 to connect any cables to the PCIe adapters.
2. Complete the parts replacement. See “Complete the parts replacement” on page 381.
Chapter 4. Hardware replacement procedures 287