Install the rear 3.5-inch drive cage
Use this information to install the rear 3.5-inch 2-bay or 4-bay drive cage.
About this task
Attention:
• Read “Installation Guidelines” on page 185 to ensure that you work safely.
• Power off the server and disconnect all power cords for this task.
• Prevent exposure to static electricity, which might lead to system halt and loss of data, by keeping static-
sensitive components in their static-protective packages until installation, and handling these devices with
an electrostatic-discharge wrist strap or other grounding system.
• The rear drive cage is supported on some server models with thermal requirements. See “Thermal rules”
on page 192 to ensure that the server is under permitted ambient temperature and the correct heat sink
and system fans are used. If needed, replace your heat sink or system fan first.
– “Processor and heat sink replacement (trained technician only)” on page 297
– “System fan cage replacement” on page 368
A video for this task is available at:
• Youtube:
https://www.youtube.com/playlist?list=PLYV5R7hVcs-DqVplE36HIvdM_sq_Auw3U
• Youku: https://list.youku.com/albumlist/show/id_59643657.html
Procedure
Step 1. (Optional) If existing rearwall brackets are not for the rear drive cage, install the rearwall brackets
that come with the rear drive cage. See “Rearwall bracket replacement” on page 322
Step 2. Install the required riser brackets. See “PCIe adapter and riser assembly replacement” on page
282.
340
ThinkSystem SR650 V2Maintenance Manual