Configuration
8200SHB01997-26
7.5.7 Configuration
Only HVAC” controllers
Code Name Possible settings IMPORTANT
C
o
d
e
N
a
m
e
Lenze Choice Info
I
M
P
O
R
T
A
N
T
C005¤ Configuration -0- -0- Operation with open-loop control via
terminal 8
-1- Operation with open-loop control via
terminal 8 with setpoint summation
via frequency input E1
-2- Operation with open-loop control via
frequency input E1 with setpoint
summation via terminal 8
If C005 = -0-
-
2mscycletime
If C005 = -1- ... -7-
-
4mscycletime
-3- Open-loop operation via frequency
input E1 with apparent current
limitation via terminal 8
C005 = -3-
possible with
C014 = -2-, -4-
-6- Operation with closed-loop control;
setpoint via terminal 8 with digital
frequency feedback via terminal E1
-7- Closed-loop operation; setpoint via
frequency input E1 with analog
feedback via terminal 8
Function The signal flow in the controller can be changed under C005. The functionality of the controller will
be changed when changing C005. The signal-flow charts in chapter 16.3 show the structure for
each configuration.
Special features The selection C005 = -4-, -5- cannot be used.