Configuration
8200SHB01997-58
7.5.14.6 Parameter set changeover PAR
Function Switches between the two parameter sets (ONLINE)during controller operation.
Activation
Series “HVAC”:
C007 = -4-, -8-, -15-, -17, -18-, or
C007 = -4-, -8-, -15-, -17-, -18-, -35-, -36-, -37-, -44-, -45- (only series “HVAC”)
- LOWlevel at terminal E2 activates PAR1
- HIGH level at terminal E2 activates PAR2
C007 = -1-, -3-, -6-, -7-, -12-, or
C007 = -1-, -3-, -6-, -7-, -12-, -24-, -33-, -38-, -46-, -51- (only series “HVAC”)
- LOWlevel at terminal E3 activates PAR1
- HIGH level at terminal E3 activates PAR2
The signal levels are indicated for C114 = -0- (see chapter 7.5.14.1)
Important
-
Inthecodeleveltheactivecodesetisindicatedbyblinkingof”PAR1”or”PAR2”.
-
The codes marked with *in the code table are similar for PAR1 and PAR2. The active parameter
set is only displayed on the operating module in the code level.
-
For changeover between the parameter sets via terminal, the same terminal of both parameter
sets must be assigned with PAR.
Special features
821X/822X/824X If the control mode (C014)is set differentlyin the parameter sets, the parameter sets should onlybe
changed when the controller is inhibited.
7.5.14.7 TRIP set
Function If the function TRIP set is activated, the unit detects external faults that can thus be taken into
account. The controller indicates the fault EEr and sets controller inhibit.
Activation
-
C007 = -7-, -8-, -18-, -19-:
-LOWlevelatterminalE1
-
C007 = -5-, -6-, -9-, -20-, or
C007 = -5-, -6-, -9-, -20-, -38-...-43- (only series “HVAC”):
-LOWlevelatterminalE2
-
C007 = -10-, or
C007 = -10-, -27- (only series “HVAC”):
-LOWlevelatterminalE3
-
C007 = -32-:
-LOWlevelatterminalE4(onlyseries“HVAC”)
Series “HVAC”: The signal levels are indicated for C114 = -0- (see chapter 7.5.14.1)
Important For fault reset, see chapter 8.4, ”Reset of fault messages”.
Special features
820X Withthe operating mode ”control via LECOM” (C001 = -3-), the function TRIP set cannot be
activated via terminals.
821X/822X/824X
Series “HVAC”:
-
Independently of the operating mode C001, TRIP set can always be activated via terminals.
-
The activation of TRIP set via terminals can be switched-off with the priority mask (C115).