Parameter Name / value range / [default seng] Info
0x2859:005
(P515.05)
EtherNet/IP monitoring: Invalid process data
(EtherN/IP monit.: Inval. proc.data)
•
From version 02.00
•
For further possible sengs, see parameter
0x2D45:001 (P310.01). ^ 223
Selecon of the response triggered by the recepon of invalid process
data.
Associated error code:
•
33171 | 0x8193 - Network: invalid cyclic process data
2 Trouble
0x2859:006
(P515.06)
EtherNet/IP monitoring: Timeout explicit message
(EtherN/IP monit.: Timeout ExplMsg)
•
From version 02.00
•
For further possible sengs, see parameter
0x2D45:001 (P310.01). ^ 223
Selecon of the response to me-outs during the transfer of Explicit
Messages.
Associated error code:
•
33042 | 0x8112 - Network: meout explicit message
1 Warning
0x2859:007
(P515.07)
EtherNet/IP monitoring: Timeout communicaon
(EtherN/IP monit.: Timeout Comm.)
•
From version 02.00
•
For further possible sengs, see parameter
0x2D45:001 (P310.01). ^ 223
Selecon of the response to the me-out during the CIP communicaon.
Selecon of the response to the me-out during the CIP communicaon.
The monitoring me for the CIP communicaon is dened in
0x23A1:010 (P510.10).
Associated error code:
•
33044 | 0x8114 - Network: overall communicaon meout
1 Warning
Conguring the network
EtherNet/IP
Monitoring