30356 0x7694 EPM data: new PU size detected Keypad display: EPM new PU size
Cause Error type/response Remedy
The parameter sengs saved in the memory
module comply with a dierent hardware.
Example: Memory module of an inverter with a
power of 3 kW is used in an inverter with a
power of 18.5 kW.
Fault
•
The data have been loaded into the RAM
memory without being modied, and they
are compable.
•
The sengs loaded must be accepted by the
user (see remedy).
1.
Check parameter sengs.
2.
Reset error.
3.
Execute "Save user data" 0x2022:003
(P700.03) or "Save OEM data" 0x2022:006
(P700.06) device command.
30357 0x7695 Invalid conguraon of parameter change-over Keypad display: InvalidChgovrCfg
Cause Error type/response Remedy
One or more parameters can no longer be used
for the "Parameter change-over" funcon.
Warning
•
The parameter change-over funcon is deac-
vated.
1.
Check error message for parameter change-
over in 0x4047:001 (P756.01).
2.
Correct the list entry shown in 0x4047:002
(P756.02).
30358 0x7696 EPM data: unknown parameter found Keypad display: Unkn. Par in EPM
Cause Error type/response Remedy
The memory module contains parameter set-
tings for one or several parameters that are not
known to the inverter.
Info Execute the "Save user data" 0x2022:003
(P700.03) device command. This reinialises
the user memory with the current parameter
sengs. In this way, parameter sengs that are
no longer required are automacally deleted.
30359 0x7697 Changed parameters lost Keypad display: Parameter loss
Cause Error type/response Remedy
A voltage failure has occurred and changed
parameter sengs that had not been saved yet
were available.
Fault
•
The inverter is inhibited immediately. The
motor becomes torqueless (coasts).
•
The parameter sengs changed have been
lost.
1.
Execute parameter sengs again.
2.
Execute device command "Save user data"
0x2022:003 (P700.03).
33042 0x8112 Network: meout explicit message Keypad display: TO expl. msg
Cause Error type/response Remedy
•
Within the me-out period for explicit mes-
sages, which has been parameterised by the
scanner, no "explicit message" was received.
•
The connecon to the scanner has been
interrupted.
•
Failure of an explicit connecon.
Warning
•
The error type can be congured in
0x2859:006 (P515.06).
•
Check cables and terminals.
•
Plug network cables into the Ethernet port.
•
Check the requested package interval (RPI) of
the explicit connecon.
•
Increase me limit for explicit messages in
the scanner.
33044 0x8114 Network: overall communicaon meout Keypad display: TO overall comm
Cause Error type/response Remedy
•
EtherNet/IP: the maximum permissible me-
out period for the CIP communicaon set in
0x23A1:010 (P510.10) has been exceeded.
•
Modbus TCP/IP: the maximum permissible
me-out period for the TCP communicaon
set in 0x23B1:010 (P510.10) has been excee-
ded.
Warning
•
The error type can be congured in
0x2859:007 (P515.07) (EtherNet/IP),
0x2859:007 (P515.07) (Modbus TCP).
•
Check cables and terminals.
•
Connect network cable.