Fuse data
Inverter I55AE355F
I55AE375F
I55AE390F
Cable installaon in compliance with EN 60204-1
Installaon method F
operaon
Fuse
Characteriscs -
Max. rated current A - -
Circuit breaker
Characteriscs - -
Max. rated current A - -
operaon with mains choke
Fuse
Characteriscs gR
Max. rated current A 160 300
Circuit breaker
Characteriscs - -
Max. rated current A - -
Earth-leakage circuit breaker
3-phase mains connecon ≥ 300 mA, type B
Fuse data
Inverter I55AE230F
I55AE240F
I55AE255F
I55AE275F I55AE311F I55AE315F
Cable installaon in compliance with US Naonal Electrical Code NFPA 70 / Canadian Electrical Code C22.1
operaon without mains choke without mains choke
Fuse
Characteriscs all acc. to UL 248 / Class
CC
all acc. to UL 248 / Class
J, T, R
-
all acc. to UL 248 / Class
J, T, R
Max. rated current A 25 40 - 70
Circuit breaker
Characteriscs -
Max. rated current A 25 35 - -
operaon with mains choke
Fuse
Characteriscs all acc. to UL 248 / Class
CC
all acc. to UL 248 / Class J, T, R
Max. rated current A 25 40 40 70
Circuit breaker
Characteriscs -
Max. rated current A 25 35 - -
Earth-leakage circuit breaker
3-phase mains connecon ≥ 300 mA, type B
Electrical installaon
Mains connecon
3-phase mains connecon 480 V "Light Duty"
60