Fuse data
Inverter I55AE318F
I55AE322F
I55AE330F I55AE337F I55AE345F
Cable installaon in compliance with US Naonal Electrical Code NFPA 70 / Canadian Electrical Code C22.1
operaon
Fuse
Characteriscs -
Max. rated current A - - - -
Circuit breaker
Characteriscs - - - -
Max. rated current A - - - -
operaon with mains choke
Fuse
Characteriscs all acc. to UL 248 / Class J, T, R
Max. rated current A 70 80 100 125
Circuit breaker
Characteriscs - - - -
Max. rated current A - - - -
Earth-leakage circuit breaker
3-phase mains connecon ≥ 300 mA, type B
Fuse data
Inverter I55AE355F
I55AE375F
I55AE390F
Cable installaon in compliance with US Naonal Electrical Code NFPA 70 / Canadian Electrical Code C22.1
operaon
Fuse
Characteriscs -
Max. rated current A - -
Circuit breaker
Characteriscs - -
Max. rated current A - -
operaon with mains choke
Fuse
Characteriscs acc. to UL 248 / Class J (recommended: HSJ by
Mersen)
all acc. to UL 248 / Class J, T, R
Max. rated current A 200 300
Circuit breaker
Characteriscs - -
Max. rated current A - -
Earth-leakage circuit breaker
3-phase mains connecon ≥ 300 mA, type B
Electrical installaon
Mains connecon
3-phase mains connecon 480 V "Light Duty"
61