Responses of the motor during performance
Remove the mechanical xaon aer the current controller has been adjusted!
The motor usually aligns itself only once with the rst controller enable.
How to adjust the current controller by means of the manual test mode "current pulse":
Disable inverter.
Calculate start parameters for the inverter based on the parameterised motor data.
The automac calculaon is made via the parameter 0x2822:013.
You can determine the start parameter manually.
Change to the "current pulse" test mode. 40x2825 = 3
Set the setpoint current for the manual test mode. 40x2835:001
Enable the inverter for a short while to start the test mode.
Measure the step response of the motor current in the motor phase U by means of an
oscilloscope and a clamp-on ammeter.
Evaluate the step response.
Adjust the gain and the reset me of the inverter.
Repeat steps 1 ... 6 unl the opmum step response of the motor current has been
reached.
Exit the test mode:
Disable the inverter.
Change to the CiA402 mode. 40x2825 = 0
For permanent saving: save changed current controller parameters.
Conguring the motor control
Tesng the motor control
Manual "curr
ent pulse" test mode