9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
252 L EDS94ARNExxxx EN 2.3 - 06/2014
CAN module (MXI2) RPDO2: Telegram not received or faulty [0x00b00001]
CAN module (MXI2) RPDO3: Telegram not received or faulty [0x00b00002]
CAN module (MXI2) RPDO4: Telegram not received or faulty [0x00b00003]
CAN module (MXI2) RPDO5: Telegram not received or faulty [0x00b00004]
CAN module (MXI2) RPDO6: Telegram not received or faulty [0x00b00005]
Response (Lenze setting printed in bold) Setting: C14591/2 ( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CANopen communication module in MXI2: CAN-IN 2
error
• Incorrect PDO telegram length.
• Transmission error.
• PDO time monitoring has responded.
• Set the correct telegram length for the CAN master
(sender).
• Eliminate disturbances in the environment (e.g. EMC).
• Select a different monitoring time or switch off time
monitoring.
Response (Lenze setting printed in bold) Setting: C14591/3 ( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CANopen communication module in MXI2: CAN-IN 3
error
• Incorrect PDO telegram length.
• Transmission error.
• PDO time monitoring has responded.
• Set the correct telegram length for the CAN master
(sender).
• Eliminate disturbances in the environment (e.g. EMC).
• Select a different monitoring time or switch off time
monitoring.
Response (Lenze setting printed in bold) Setting: C14591/4 ( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CANopen communication module in MXI2: CAN-IN 4
error
• Incorrect PDO telegram length.
• Transmission error.
• PDO time monitoring has responded.
• Set the correct telegram length for the CAN master
(sender).
• Eliminate disturbances in the environment (e.g. EMC).
• Select a different monitoring time or switch off time
monitoring.
Response (Lenze setting printed in bold) Setting: C14591/5 ( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CANopen communication module in MXI2: CAN-IN 5
error
• Incorrect PDO telegram length.
• Transmission error.
• PDO time monitoring has responded.
• Set the correct telegram length for the CAN master
(sender).
• Eliminate disturbances in the environment (e.g. EMC).
• Select a different monitoring time or switch off time
monitoring.
Response (Lenze setting printed in bold) Setting: C14591/6 ( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CANopen communication module in MXI2: CAN-IN 6
error
• Incorrect PDO telegram length.
• Transmission error.
• PDO time monitoring has responded.
• Set the correct telegram length for the CAN master
(sender).
• Eliminate disturbances in the environment (e.g. EMC).
• Select a different monitoring time or switch off time
monitoring.