9400 regenerative power supply module | Parameter setting
I/O terminals
Digital inputs
94 L EDS94ARNExxxx EN 2.3 - 06/2014
5.4 Digital inputs
The regenerative power supply module is equipped with 8 freely configurable digital
inputs.
Control input RFR of terminal strip X5 for controller enable is permanently connected
to the device control.
5.4.1 Terminal assignment/electrical data
5.4.2 Parameter setting
Short overview of parameters for the digital inputs:
Terminal Use Electrical data
X5/DI1
X5/DI8
Digital input 1 ... 8 LOW level: 0 ... +5 V
HIGH level: +15 ... +30 V
Input current: 8 mA per input
(at 24 V)
Interference-voltage-
proof:
max. ±30 V
Conversion rate: 1 kHz
X5/RFR Controller enable See digital inputs
X5/GI Reference potential (digital ground)
X5
GI
RFR
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
Parameter Information
C00114
Dig. input x: Terminal polarity
C00443 Status: Digital inputs
C02803 Status word: Digital inputs
C02830
Digital inputs: Delay time
Highlighted in grey = display parameter