EDS94ARNExxxx EN 2.3 - 06/2014 L 95
9400 regenerative power supply module | Parameter setting
I/O terminals
Digital outputs
5.5 Digital outputs
The regenerative power supply module is equipped with 4 freely configurable digital
outputs.
5.5.1 Terminal assignment/electrical data
5.5.2 Parameter setting
Short overview of parameters for the digital outputs:
Note!
Initialisation behaviour:
• After mains switching until the start of the application, the digital outputs
remain set to FALSE.
Exception handling:
• In the case of a critical exception within the application (e.g. reset), the digital
outputs are set to FALSE, taking the terminal polarity parameterised in
C00118
into consideration.
Terminal Use Electrical data
X4/DO1
...
X4/DO4
Digital output 1 ... 4 LOW level: 0 ... +5 V
HIGH level: +15 ... +30 V
Output current: max. 50 mA per output (external
resistance > 480 Ω at 24 V)
Conversion rate: 1 kHz
X4/24O External 24 V voltage supply for the digital outputs
X4/GO Reference potential (digital ground)
Parameter Information
C00118
Dig. output x: Terminal polarity
C00444 Status: Digital outputs
C02802 Status word: Digital outputs
Highlighted in grey = display parameter