EDS94ARNExxxx EN 2.3 - 06/2014 L 39
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
4.1.1 Load Lenze setting
The C00002
= "0: Load Lenze setting" device command can be used to reset the parameters
of the active application to the Lenze setting which is stored in the firmware of the
regenerative power supply module:
[4-1] "Load Lenze setting" function
Only possible when the controller is inhibited and the application has been stopped.
All parameter changes made since the last saving of the parameter set will get lost!
This device command only has an impact on the settings of the operating system,
application, and module parameters, the active application remains unchanged.
Possible status displays for this device command
Related device commands
Load start parameters
( 40)
Save start parameters
( 44)
Application 3
PS
Application 2
PS
Memory module MM
PS
9400
PS
RAM
Firmware Application 1Application
PS
Status (C00003) Meaning
34050 Device command in process
0 Device command executed successfully
1 General fault
39424 CAN fault
... ...
39679 CAN fault