9400 regenerative power supply module | Parameter setting
"CAN on board" system bus
Parameter data transfer
128 L EDS94ARNExxxx EN 2.3 - 06/2014
6.7.3 Parameter data telegram examples
6.7.3.1 Read parameters
Task:
The heatsink temperature (43 °C) of the controller with the node address "5" is to be
read (code C00061, data format INTEGER32, scaling factor 1).
Telegram to the drive
Response telegram from the drive (for successful execution)
Identifier User data
1st byte 2nd byte 3rd byte 4th byte 5th byte 6th byte 7th byte 8th byte
Command Index Subindex Data 1 Data 2 Data 3 Data 4
0x0605 0x40 0xC2 0x5F 0x00 0x00 0x00 0x00 0x00
Explanations - telegram to drive
Identifier = 1536 + node address = 1536 + 5 = 1541 = 0x0605
(1536 = basic identifier of SDO1 to the controller)
Command = 0x40 = "read request" (request to read a parameter from the controller)
Index = 24575 - code number = 24575 - 61 = 24514 = 0x5FC2
Subindex = 0 (code C00061 has no subcodes)
Identifier User data
1st byte 2nd byte 3rd byte 4th byte 5th byte 6th byte 7th byte 8th byte
Command Index Subindex Data 1 Data 2 Data 3 Data 4
0x0585 0x43 0xC2 0x5F 0x00 0x2B 0x00 0x00 0x00
Explanations - telegram from drive
Identifier = 1408 + node address = 1408 + 5 = 1413 = 0x0585
(1408 = basic identifier of SDO1 from the controller)
Command = 0x43 = "read response" (response to the read request with the current value)
Index Same as for telegram to the drive
Subindex
Data 1 ... 4 = 0x0000002B = 43 [°C]