9400 regenerative power supply module | Parameter setting
I/O terminals
Analog outputs
92 L EDS94ARNExxxx EN 2.3 - 06/2014
5.3 Analog outputs
The regenerative power supply module is provided with 2 analog outputs which can be
used to output internal analog signals as voltage signals, e.g. for display via analog
indicating instruments.
5.3.1 Terminal assignment/electrical data
Note!
Initialisation behaviour:
• After mains switching until the start of the application, the analog outputs
remain set to 0 V.
Exception handling:
• In the case of a critical exception within the application (e.g. reset), the analog
outputs are set to 0 V.
Terminal Use Electrical data
X3/AO1 Voltage output 1 Level: -10 V ... +10 V
(max. 2 mA)
Resolution: 11 bits + sign
Scaling: ±2
30
≡ ±10 V
Conversion rate: 1 kHz
X3/AO2 Voltage output 2 Level: -10 V ... +10 V
(max. 2 mA)
Resolution: 11 bits + sign
Scaling: ±2
30
≡ ±10 V
Conversion rate: 1 kHz
X3/GA Reference potential (analog ground)