9400 regenerative power supply module | Parameter setting
"CAN on board" system bus
Possible settings via DIP switches
6.2 Possible settings via DIP switches
The front panel DIP switches of the memory module serve to set the baud rate and the
node address:
[6-1] DIP switches
6.2.1 Setting the node address
The node address can be set via code C00350
or via the DIP switches 1 ... 64.
The labelling on the housing corresponds to the values of the individual DIP switches
for setting the node address.
Valid address range: 1 … 127
Example: setting node address 23
Tip!
The node address resulting from the setting of the DIP switches at the last mains
switching is displayed in C00349/1
.
Baud
CAN Address
O
N
cdba
64
32
16 8
421
Note!
The addresses of the nodes must differ from each other.
•All
twelve DIP switches = OFF (Lenze setting):
On switching on, the settings of codes C00350
(node address) and C00351
(baud rate) are active.
Switch off the voltage supply of the standard device and then on again to
activate changed settings.
DIP switch 64 32 16 8 4 2 1
Switch position OFF OFF ON OFF ON ON ON
Value 0 0
16 0 4 2 1
Node address = sum of all values = 16 + 4 + 2 + 1 = 23