9400 regenerative power supply module | Parameter setting
Device interface
Device states
80 L EDS94ARNExxxx EN 2.3 - 06/2014
Display parameters for diagnostic purposes
The current device state is displayed in C00183
.
C00150
(status word 1) displays the current device state in a bit-coded manner via
bits 8 ... 11:
4.2.1 State "Initialisation active"
This is the device state of the regenerative power supply module directly after switching
on the supply voltage.
In this device state the operating system is initialised.
The application is not processed yet.
The monitoring mode is not active yet.
Communication is not possible yet.
The regenerative power supply module cannot be parameterised yet and no device
commands can be executed.
When the device initialisation is completed, the device state is automatically changed
to "Device is ready to switch on".
Bit 11 Bit 10 Bit 9 Bit 8 Meaning
0000State "Initialisation active"
0001State "Device is ready to switch on"
0010-
0011State "Device is switched on"
0100-
0101-
0110State "Operation"
0111State "Warning active" or State "Warning locked active"
The regenerative power supply module is ready to switch on,
switched on, or operation is enabled and a warning is indicated.
1000State "Trouble active"
1001-
1010-
1011-
1100State "Fault active"
1101-
1110-
1111-
LED DRIVE READY LED DRIVE ERROR Display in C00183
OFF OFF 10: Initialisation active