9400 regenerative power supply module | Parameter setting
Device interface
Automatic restart after power-on/trouble/fault
84 L EDS94ARNExxxx EN 2.3 - 06/2014
4.3 Automatic restart after power-on/trouble/fault
C00142
serves to parameterise the starting performance of the regenerative power supply
module after power-on or after resetting a "Trouble" or "Fault".
Auto-start option 1: auto-restart enabled after power-on
The following illustration shows the state change for the auto-start option 1 (Lenze
setting) as a function of controller inhibit:
[4-12] State change when auto-restart is enabled (C00142 = "1: Enabled")
Pulses of the regenerative power supply module are inhibited
Pulses of the regenerative power supply module are enabled
With controller inhibit at power-on
Without controller inhibit at power-on
RFR
01
RFR
RFR
RFR
t
t
Initialisation Switched on OperationReady to switch on
OperationInitialisation Switched onReady to switch on