9400 regenerative power supply module | Parameter setting
Parameter reference
Parameter list | C00180
288 L EDS94ARNExxxx EN 2.3 - 06/2014
C00180
C00181
C00183
C00186
C00187
Parameter | Name:
C00180 | Service code
Data type: VISIBLE_STRING
Index: 24395
d
= 5F4B
h
For Lenze service only
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00181 | Red. brake chopper threshold
Data type: UNSIGNED_32
Index: 24394
d
= 5F4A
h
Parameterising the brake chopper/brake resistor
Setting range (min. value | unit | max. value) Lenze setting
0 V 100 0V
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00183 | Device state
Data type: UNSIGNED_32
Index: 24392
d
= 5F48
h
Display of the device state for diagnostic purposes
Selection list (display only)
0 Operation
1 Operation/Warning active
2 Operation/warning locked act.
3 Reserved
4 Operation/Application stopped
10 Initialisation active
20 System fault active
90 Drive switched on
91 Reserved
101 Power regeneration blocked
102 Fault active
104 Trouble active
141 Drive ready to start --> C00142
151 Reserved
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00186 | ENP: Identified filter type
Data type: VISIBLE_STRING
Index: 24389
d
= 5F45
h
Filter type read from the electronic nameplate (ENP)
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00187 | ENP: Identified serial number
Data type: VISIBLE_STRING
Index: 24388
d
= 5F44
h
Serial number read from the electronic nameplate (ENP)
Read access Write access CINH PLC STOP No transfer