Code
Comm.
Address
Name
Setting Range
Initial
Value
Property*
V/F
SL
Ref.
Pr-13
43
0h1B0D
Time to
determine
speed
command
loss
0.1120 (s)
1.0
O
O
O
p.189
Pr-14
43
0h1B0E
Operation
frequency at
speed
command
loss
0, Start
frequency
Maximum
frequency(Hz)
0.00
O
O
O
p.189
Pr-15
43
0h1B0F
Analog input
loss decision
level
0
Half of x1
0: Half
of x1
O
O
O
p.189
1
Below x1
Pr-17
0h1B11
Overload
warning
selection
0
No
0: No
O
O
O
p.179
1
Yes
Pr-18
0h1B12
Overload
warning level
30180 (%)
150
O
O
O
p.179
Pr-19
0h1B13
Overload
warning time
0.030.0 (s)
10.0
O
O
O
p.179
Pr-20
0h1B14
Motion at
overload fault
0
None
1: Free-
Run
O
O
O
p.179
1
Free-Run
2
Dec
Pr-21
0h1B15
Overload
fault level
30200 (%)
180
O
O
O
p.179
Pr-22
0h1B16
Overload
fault time
0.060.0 (s)
60.0
O
O
O
p.179
Pr-25
0h1B19
Under load
warning
selection
0
No
0: No
O
O
O
p.194
1
Yes
Pr-26
0h1B1 A
Under load
warning time
0.0600.0 (s)
10.0
O
O
O
p.194
Pr-27
0h1B1B
Under load
fault selection
0
None
0: None
O
O
O
p.194
1
Free-Run
2
Dec
Pr-28
0h1B1C
Under load
fault time
0.0600.0 (s)
30.0
O
O
O
p.194
Pr-29
0h1B1D
Under load
lower limit
level
10100 (%)
30
O
O
O
p.194
43