Appendix 7. Explanation of Alarms
Appendix 7.10 Multi CPU Errors (A)
A01 MULTI CPU ERROR 3300
Details
- The head I/O number in the intelligent function module parameter set on GX Configurator
differs from the actual I/O number.
Remedy
- Check the parameter setting.
A01 MULTI CPU ERROR 3301
Details
- The refresh setting of the intelligent function module exceeded the file register capacity.
Remedy
- Change the file register file for the one which allows refresh in the whole range.
Details
- The intelligent function module's refresh parameter setting is outside the available range.
Remedy
- Check the parameter setting.
A01 MULTI CPU ERROR 3302
Details
- The intelligent function module's refresh parameter is abnormal.
Remedy
- Check the parameter setting.
A01 MULTI CPU ERROR 3303
Details
- In a multiple CPU system, the automatic refresh setting or other parameter setting was
made to the intelligent function module under control of another station.
Remedy
- Delete the automatic refresh setting or other parameter setting of the intelligent function
module under control of another CPU.
- Change the setting to the automatic refresh setting or other parameter setting of the
intelligent function module under control of the host CPU.
A01 MULTI CPU ERROR 3400
Details
- The head I/O number of the target module in the remote password file is set to other than
0H to 0FF0H.
Remedy
- Change the head I/O number of the target module to within the 0H to 0FF0H range.