IV - 151
Appendix 7. Explanation of Alarms
Appendix 7.11 Network Errors (L)
L11 DN INIT. ERR. 2 02 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The number of input points and output points of the slave node set by parameters are both
"0".
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit
removed.
Remedy
- Set the number of input points and output points according to the slave node
specifications.
L11 DN INIT. ERR. 2 03 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The lower byte of the slave node No. in the buffer memory is out of range.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit
removed.
Remedy
- Set it between 0 and 63.
L11 DN INIT. ERR. 2 04 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The higher byte of the slave node No. in the buffer memory is out of range.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit
removed.
Remedy
- Set it between 01H and 04H, or to 80H.
L11 DN INIT. ERR. 2 05 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The connection type in the buffer memory is out of range.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit
removed.
Remedy
- Set it to one of the following: 0001H, 0002H, 0004H, or 0008H.
L11 DN INIT. ERR. 2 06 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- A slave node having the same node No. as the node No. of the local node is set in the
buffer memory.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit
removed.
Remedy
- Set non-duplicate node Nos. in all nodes.

Table of Contents