EasyManuals Logo

Mitsubishi C70 User Manual

Mitsubishi C70
536 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #499 background imageLoading...
Page #499 background image
IV - 154
Appendix 7. Explanation of Alarms
Appendix 7.11 Network Errors (L)
L11 DN INIT. ERR. 2 11 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The number of output points per slave node has exceeded 256 bytes.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit
removed.
Remedy
- Correct the number of output points per slave node to 256 bytes or less.
L11 DN INIT. ERR. 2 15 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The production inhibit time value was set to 0 ms (setting value "1") in cyclic.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit
removed.
Remedy
- Set the production inhibit time value to a value other than 0 ms.
L11 DN INIT. ERR. 2 16 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- Slave nodes that were set by parameters are all reserved nodes.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit
removed.
Remedy
- Set the parameters according to the slave nodes connected to the network.
L11 DN INIT. ERR. 2 80 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The number of reception bytes of the slave function is out of range.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit
removed.
Remedy
- Set it within the range between 0 and 128 bytes.
L11 DN INIT. ERR. 2 81 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The number of transmission bytes of the slave function is out of range.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit
removed.
Remedy
- Set it within the range between 0 and 128 bytes.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi C70 and is the answer not in the manual?

Mitsubishi C70 Specifications

General IconGeneral
BrandMitsubishi
ModelC70
CategoryControl Unit
LanguageEnglish

Related product manuals