IV - 154
Appendix 7. Explanation of Alarms
Appendix 7.11 Network Errors (L)
L11 DN INIT. ERR. 2 11 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The number of output points per slave node has exceeded 256 bytes.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit
removed.
Remedy
- Correct the number of output points per slave node to 256 bytes or less.
L11 DN INIT. ERR. 2 15 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The production inhibit time value was set to 0 ms (setting value "1") in cyclic.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit
removed.
Remedy
- Set the production inhibit time value to a value other than 0 ms.
L11 DN INIT. ERR. 2 16 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- Slave nodes that were set by parameters are all reserved nodes.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit
removed.
Remedy
- Set the parameters according to the slave nodes connected to the network.
L11 DN INIT. ERR. 2 80 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The number of reception bytes of the slave function is out of range.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit
removed.
Remedy
- Set it within the range between 0 and 128 bytes.
L11 DN INIT. ERR. 2 81 (Error-detected module I/O No.)
Details
A deviceNet initialization error has occurred. The error-detected node No. is FEH.
- The number of transmission bytes of the slave function is out of range.
"Error-detected module I/O No." shows the error-detected module I/O No. with the last digit
removed.
Remedy
- Set it within the range between 0 and 128 bytes.