FX3U Series Programmable Controllers
User’s Manual - Hardware Edition
110
6 Examination of System Configuration
6.9 Example of System Configuration and System Modification
3 Calculate the number of input/output points.
Calculate the number of input/output points on the whole system.
1. Calculate the number of input/output points of the main unit and extension devices.
2. Calculate the number of remote I/O points on the network.
Since this system uses CC-Link, calculate the number of the remote I/O stations.
3. Calculate the total number of input/output occupied points (number of input/output points).
+
48 points
128 points
256 points
Max. number of
input/output points
Number of input/output points
176 points
Calculation result
=
A
OK
Main unit
Total input/output points
of extension devices
1-
1
2-
1
1 station
224 points
Number of CC-Link
remote I/O stations
Input/output on network
×
32 points
FX
2N
-16CCL-M: up to 7 stations
=
Calculation result
32 points
B
OK
Max. number of
input/output points
176 points
384 points
Number of input/output
occupied points
+
Input/output on network
32 points
BA
Total obtained in Step 1 Total obtained in Step 2
Total number of input/output points
OK
=
208 points
Calculation
result
Max. number of
input/output points

Table of Contents

Other manuals for Mitsubishi FX3U Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3U Series and is the answer not in the manual?

Mitsubishi FX3U Series Specifications

General IconGeneral
ModelFX3U Series
Program Memory64k steps
Execution Speed0.065 μs/basic instruction
TypePLC (Programmable Logic Controller)
Power Supply100-240V AC
I/O PointsUp to 384
CommunicationUSB
ExpansionSupported via expansion modules
High-Speed CountersUp to 6 channels
Analog Input/OutputAvailable via expansion modules
Temperature Range0 to 55°C
Programming LanguageLadder Logic, Structured Text
Built-in FunctionsPID control
Humidity5 to 95% (non-condensing)

Related product manuals